More Info
Residential Light Commercial Commercial Back
Toshiba - Leading Innovation
Home Services Enquiries Downloads Toshiba Products Contact Links
Toshiba Products
VRF (Commercial) - Heat Recovery Outdoor Units Residential

  • Low weight, compact design
  • 48 Modular indoor units maximum, 8 to 30 hp to be combined with up to 135% of the outdoor unit capacity
  • Superior EER for reduced energy consumption and increased savings
  • High-lift design, greater location flexibility
  • State-of-the-art communication bus system with automatically configured addressing
  • Low noise level, energy class A
  • Outdoor unit dimensions match the S-MMS
  • Added flexibility and control with flow selectors and piping branches




Rating   8 10 12
Heat recovery model MMY   MAP0802FT8-E MAP01002FT8-E MAP01202FT8-E

Cooling Capacity kW 22.4 28.0 33.5
Heating Capacity kW 25.0 31.5 37.5
Min. / max. capacity code* hp 5.6 - 10.8 7.0 - 13.5 8.4 - 14.4

Power input, cooling / heating kW 6.07 / 6.29 8.54 / 8.73 12.90 / 9.65
Max. running current, cooling / heating A 9.25 / 9.55 13.15 / 13.40 19.85 / 14.85
EER, Cooling / COP, heating kw / kw 3.69 / 3.97 3.18 / 3.61 2.60 / 3.68

Sound Pressure Level, cooling / heating dB(A) at 1m 57 / 57 58 / 58 58 / 59
Sound Power Level (Low/Medium/High dB(A) 70 / 70 71 / 71 72 / 72

UK Conditions - Cooling Capacity kW 21.44 26.80 32.16
UK Conditions - Sensible Cooling Capacity kW 16.08 20.10 24.12
UK Conditions - Heating Capacity kW 20.72 25.90 31.08

Refrigerant charge R410A, heating  kg 11.5 11.5 11.5

Dimensions, Height x Width x Depth mm 1800 x 990 x 750 1800 x 990 x 750 1800 x 990 x 750
Weight kg 258 258 258

Pipe connections        
Suction line type - diameter  in Brazed - 7/8 Brazed - 7/8 Brazed - 7/8
Liquid line type - diameter  in Flare - 1/2 Flare - 1/2 Flare - 1/2
Discharge lineconnection type - diameter in  Flare - 3/4 Flare - 3/4 Flare - 3/4

Maximum equivalent pipe length m 150 150 150
Maximum actual pipe length m 125 125 125
Maximum total pipe length m 250 250 250
Max. heaight difference - indoor unit above / below m 30 / 50 30 / 50 30 / 50

Operating range, cooling °C -5 to 43 db -5 to 43 db -5 to 43 db
Operating range, heating °C -20 to 16 wb -20 to 16 wb -20 to 16 wb

Max. operating current per phase A 9.55 13.40 19.85
Starting current per phase A 1 1 1
Suggested fuse size per phase m 16 20 25
Power supply V-ph-Hz 415 - 3 - 50 415 - 3 - 50 415 - 3 - 50
Supply To   Outdoor Unit Outdoor Unit Outdoor Unit
Interconnecting cables   2 - core twisted screened

Retail price  
Outdoor Unit £ 6,212.00 6,756.00 8,258.00

Flow selector Capacity, kw Max. No of connected units Retail price £
RBM-Y1122FE 0 to 11.2 5 442.00
RBM-Y1802FE 11.2 to 18.0 8 490.00
RBM-Y2802FE 18.0 to 28.0 8 770.00

© Copyright Blue Glass Web Services 2007-2008 | www.bgwebservices.com