| Indoor units MMD | AP0181H | AP0241H | AP0271H | AP0361H | AP0481H |
| Capacity code | hp | 2 | 2.5 | 3 | 4 | 5 |
| Cooling Capacity | kW | 5.6 | 7.1 | 8.0 | 11.2 | 14.0 |
| Heating Capacity | kW | 6.3 | 8.0 | 9.0 | 12.5 | 816.0 |
| Power input | kW | 0.184 | 0.299 | 0.299 | 0.368 | 0.414 |
| Air flow (high / medium / low) | l/s | 300 / 250 / 100 | 439 / 367 / 295 | 439 / 367 / 295 | 533 / 445 / 356 | 700 / 583 / 467 |
| Air flow (high / medium / low) | m3/h | 1080 / 900 / 720 | 1580 / 1320 / 1060 | 1580 / 1320 / 1060 | 1920 / 1600 / 1280 | 2520 / 2100 / 1680 |
| Sound pressure level (high / medium / low) | db(A) | 37 / 35 / 33 | 40 / 38 / 36 | 40 / 38 / 36 | 40 / 38 / 36 | 40 / 38 / 36 |
| Sound power level (high / medium / low) | db(A) | 50 / 48 / 46 | 53 / 51 / 49 | 53 / 51 / 49 | 53 / 51 / 49 | 53 / 51 / 49 |
| Dimensions, height x width x depth | mm | 380 x 850 x 660 | 380 x 850 x 660 | 380 x 850 x 660 | 380 x 850 x 660 | 380 x 1200 x 660 |
| Weight, unit | kg | 50 | 52 | 52 | 56 | 67 |
| Max. operating current | A | 0.81 | 1.35 | 1.35 | 1.63 | 1.84 |
| Starting current | A | 1.3 | 3.5 | 3.5 | 4.1 | 04.8 |
| Suggested fuse size | A | 3 | 5 | 5 | 5 | 10 |
| Power supply | V - p h- Hz | 220/240 -1- 50 | 220/240 - 1 - 50 | 220/240 -1 - 50 | 220/240 - 1 - 50 | 220/240 - 1 - 50 |
| Retail Price | ||||||
| Indoor unit | £ | 1,229.00 | 1,282.00 | 1,457.00 | 1.641.00 | 1,772.00 |
| Indoor units MMU | AP0721H | AP0961H |
| Capacity code | hp | 8 | 10 |
| Cooling Capacity | kW | 22.4 | 28.0 |
| Heating Capacity | kW | 25.0 | 31.5 |
| Power input | kW | 1.200 | 1.260 |
| Air flow (high / medium / low) | l/s | 1200 / 1000 / 800 | 1400 / 1167 / 933 |
| Air flow (high / medium / low) | m3/h | 4320 / 3600 / 2880 | 5040 / 4200 / 3360 |
| Sound pressure level (high / medium / low) | db(A) | 49 / 47 / 45 | 50 / 48 / 46 |
| Sound power level (high / medium / low) | db(A) | 62 / 60 / 58 | 63 / 61 / 59 |
| Dimensions, height x width x depth | mm | 470 x 1200 x 1250 | 470 x 1200 x 1250 |
| Weight | kg | 150 | 150 |
| Max. operating current | A | 5.25 | 5.52 |
| Starting current | A | 13.6 | 14.8 |
| Suggested fuse size | A | 16 | 16 |
| Power supply | V - p h- Hz | 220/240 -1- 50 | 220/240 - 1 - 50 |
| Retail Price | |||
| Indoor unit | £ | 2,784.00 | 2,996.00 |