More Info
Residential Light Commercial Commercial Back
Toshiba - Leading Innovation
Home Services Enquiries Downloads Toshiba Products Contact Links
Toshiba Products

Mini-SMMS System - VRF Heat Pump Outdoor UnitsResidential

  • Single phase power supply
  • Compact and light-weight outdoor unit
  • High-efficiency DC twin rotary compressor
  • Best COP in the industry: 4.61
  • Capacity range 12-15.5kw cooling and 12.18kw heating
  • Automatic addressing
  • Extended refrigerant piping capability
  • Operates up to nine indoor units from a choice of over 80
  • Ultra-quiet, utilising remote PMV kit (option)
  • Designed for use with refrigerant R410A
  • All systems acheive energy efficiency class A


Rating  HP 4 5 6
Heat pump model MCY   MAP0401HT MAP0501HT MAP0601HT

Cooling Capacity kW 12.1 14.0 15.5
Heating Capacity kW 12.5 16.0 18.0
Min. / max. capacity code** hp 3.2 - 5.2 4.0 - 6.5 4.3 - 7.8

Power input, cooling / heating kW 2.82 / 2.71 3.47 / 4.0 4.63 / 4.85
Max. running current, cooling / heating A 13.2 / 12.5 16.1 / 118.3 21.4 / 22.2
EER, Cooling / COP, heating kw / kw 4.29 / 4.61 4.03 / 4.00 3.35 / 3.71
Energy label, cooling / heating kw / kw A / A A / A A / A

Sound Pressure Level, cooling / heating dB(A) at 1m 49 / 50 58 / 58 51 / 53
Sound Power Level (Low/Medium/High dB(A) 62 / 63 63 / 65 64 / 66

UK Conditions - Cooling Capacity kW 11.59 13.42 14.35
UK Conditions - Sensible Cooling Capacity kW 8.70 10.06 11.14
UK Conditions - Heating Capacity kW 10.12 12.96 14.58

Refrigerant charge R410A, heating  kg 7.2 7.2 7.2

Dimensions, Height x Width x Depth mm 1340 x 990 x 7320 1340 x 990 x 7320 1340 x 990 x 7320
Weight kg 117 117 117

Pipe connections        
Suction line type - diameter  in Brazed - 5/8 Brazed - 5/8 Brazed - 3/4
Liquid line type - diameter  in Flare - 3/8 Flare - 3/8 Flare - 3/8

Maximum equivalent pipe length m 125 125 125
Maximum actual pipe length m 100 100 100
Maximum total pipe length m 180 180 180
Max. heaight difference - indoor unit above / below** m 30 / 20 30 / 20 30 / 20

Operating range, cooling °C -10 to 43 db -10 to 43 db -10 to 43 db
Operating range, heating °C -15 to 120 wb -15 to 120 wb -15 to 120 wb

Max. operating current per phase A 13.8 19.1 23.2
Starting current per phase A 1 1 1
Suggested fuse size per phase m 16 25 25
Power supply V-ph-Hz 220/240 -1- 50 220/240 -1- 50 220/240 -1- 50
Supply To   Outdoor & indoor Unit Outdoor & indoor Unit Outdoor & indoor Unit
Interconnecting cables   2 - core twisted screened

* Codes are basded on individual units and do not take into consideration modular applications
 
** If the indoor unit is above, maximum lift is reduced to 30m, if height difference between indoor units exceeds 3m
Retail price  
Outdoor Unit £ 3,640.00 4,135.00 4,450.00

External PMV valve   Capacity, kw Retail price, £  
RBM-PMV0361E   2.2 - 3.6 150.00  
RBM-PMV0901E   4.5 - 5.0 162.00  


© Copyright Blue Glass Web Services 2007-2008 | www.bgwebservices.com