Mini-SMMS System - VRF Heat Pump
Outdoor Units
- Single phase power supply
- Compact and light-weight outdoor unit
- High-efficiency DC twin rotary compressor
- Best COP in the industry: 4.61
- Capacity range 12-15.5kw cooling and 12.18kw heating
- Automatic addressing
- Extended refrigerant piping capability
- Operates up to nine indoor units from a choice of over 80
- Ultra-quiet, utilising remote PMV kit (option)
- Designed for use with refrigerant R410A
- All systems acheive energy efficiency class A
| Rating |
HP |
4 |
5 |
6 |
| Heat pump model MCY |
|
MAP0401HT |
MAP0501HT |
MAP0601HT |
| Cooling Capacity |
kW |
12.1 |
14.0 |
15.5 |
| Heating Capacity |
kW |
12.5 |
16.0 |
18.0 |
| Min. / max. capacity code** |
hp |
3.2 - 5.2 |
4.0 - 6.5 |
4.3 - 7.8 |
| Power input, cooling / heating |
kW |
2.82 / 2.71 |
3.47 / 4.0 |
4.63 / 4.85 |
| Max. running current, cooling / heating |
A |
13.2 / 12.5 |
16.1 / 118.3 |
21.4 / 22.2 |
| EER, Cooling / COP, heating |
kw / kw |
4.29 / 4.61 |
4.03 / 4.00 |
3.35 / 3.71 |
| Energy label, cooling / heating |
kw / kw |
A / A |
A / A |
A / A |
| Sound Pressure Level, cooling / heating |
dB(A) at 1m |
49 / 50 |
58 / 58 |
51 / 53 |
| Sound Power Level (Low/Medium/High |
dB(A) |
62 / 63 |
63 / 65 |
64 / 66 |
| UK Conditions - Cooling Capacity |
kW |
11.59 |
13.42 |
14.35 |
| UK Conditions - Sensible Cooling Capacity |
kW |
8.70 |
10.06 |
11.14 |
| UK Conditions - Heating Capacity |
kW |
10.12 |
12.96 |
14.58 |
| Refrigerant charge R410A, heating |
kg |
7.2 |
7.2 |
7.2 |
| Dimensions, Height x Width x Depth |
mm |
1340 x 990 x 7320 |
1340 x 990 x 7320 |
1340 x 990 x 7320 |
| Weight |
kg |
117 |
117 |
117 |
| Pipe connections |
|
|
|
|
| Suction line type - diameter |
in |
Brazed - 5/8 |
Brazed - 5/8 |
Brazed - 3/4 |
| Liquid line type - diameter |
in |
Flare - 3/8 |
Flare - 3/8 |
Flare - 3/8 |
| Maximum equivalent pipe length |
m |
125 |
125 |
125 |
| Maximum actual pipe length |
m |
100 |
100 |
100 |
| Maximum total pipe length |
m |
180 |
180 |
180 |
| Max. heaight difference - indoor unit above / below** |
m |
30 / 20 |
30 / 20 |
30 / 20 |
| Operating range, cooling |
°C |
-10 to 43 db |
-10 to 43 db |
-10 to 43 db |
| Operating range, heating |
°C |
-15 to 120 wb |
-15 to 120 wb |
-15 to 120 wb |
| Max. operating current per phase |
A |
13.8 |
19.1 |
23.2 |
| Starting current per phase |
A |
1 |
1 |
1 |
| Suggested fuse size per phase |
m |
16 |
25 |
25 |
| Power supply |
V-ph-Hz |
220/240 -1- 50 |
220/240 -1- 50 |
220/240 -1- 50 |
| Supply To |
|
Outdoor & indoor Unit |
Outdoor & indoor Unit |
Outdoor & indoor Unit |
| Interconnecting cables |
|
2 - core twisted screened |
| * Codes are basded on individual units and
do not take into consideration modular applications |
| ** If the indoor unit is above, maximum lift is reduced
to 30m, if height difference between indoor units exceeds 3m |
| Retail price |
|
| Outdoor Unit |
£ |
3,640.00 |
4,135.00 |
4,450.00 |
| External PMV valve |
|
Capacity, kw |
Retail price, £ |
|
| RBM-PMV0361E |
|
2.2 - 3.6 |
150.00 |
|
| RBM-PMV0901E |
|
4.5 - 5.0 |
162.00 |
|