More Info
Residential Light Commercial Commercial Back
Toshiba - Leading Innovation
Home Services Enquiries Downloads Toshiba Products Contact Links
Toshiba Products
Light Commercial - Heat Pump Systems, High-Wall Units Residential
  • Attractive, slim-line flat-panel, ideal for offices, shops and reataurants
  • High-performance operation, using digital inverter control system
  • Enhanced indoor air quality is acheived with Toshiba's five-stage filtration system
  • Auto louvre mode ensures even air distribution throughout the room pan
  • Designed for use with R410A
  • Twin-split and triple-split also available*
  • Wireless controller included
  • Ideal for R22 replacement



Outdoor Unit RAV SM563AT-E SM803AT-E
Indoor Unit (ducted) RAV SM562KRT-E SM802KRT-E
Remote Control Infra-red Infra-red

Cooling Capacity Range kW 5.1 (1.5-5.6) 6.7 (1.5-8.0)
Heating Capacity Range kW 5.6 (1.5-6.3) 8.0 (1.5-9.0)
Power Input , cooling / heating kW 1.74 / 1.70 2.72 / 2.67
EER, Cooling / COP, heating W/W 2.93 / 3.29 2.46 / 3.00
Annual Power consumption, cooling kWh 870 1360
Energy Label, cooling / heating C/C E/D

UK Conditions - Cooling Capacity kW 5.44 7.76
UK Conditions - Sensible Cooling Capacity kW 4.22 5.85
UK Conditions - Heating Capacity kW 4.69 6.70

Indoor Unit (cassette) RAV SM562KRT-E SM802KRT-E

Air Flow (High/Medium/Low) l/s 178/208/233 203/243/308
Air Flow (High/Medium/Low) m3/h 641/6749/839 731/875/1109

Sound Pressure Level (Low/Medium/High) dB(A) 33/36/39 36/41/45
Sound Power Level (Low/Medium/High dB(A) 48/51/54 51/56/60

Dimensions, Height x Width x Depth mm 298 x 998 x 208 298 x 998 x 208
Weight kg 12 12
Dimensions, Height x Width x Depth mm 250 x 740 x 185 275 x 790 x 218
Dimensions, Height x Width x Depth mm 250 x 740 x 185 275 x 790 x 218

Dimensions, Height x Width x Depth mm 250 x 740 x 185 275 x 790 x 218

Outdoor Unit RAV SM563AT-E SM803AT-E

Airflow l/s (m3/h) 667 (2400) 750 (2700)
Sound Pressure Level, cooling / heating dB (A) 46/ 48 48/ 50
Sound Power Level, cooling / heating dB (A) 63/ 65 65 / 67

Dimensions, Height x Width x Depth mm 550 x 780 x 290 550 x 780 x 290
Weight kg 38 42

Operating Range - Cooling °C -15 to 43 -15 to 43
Operating Range - Heating °C -15 to 15 -15 to 15

Pipe Connections, Gas - Liquid in 1/2 - 1/4 5/8 - 3/8
Pipe Length, Maximum / Minimum m 30/5 30/5
Pipe length, pre-charged m 20 20
Additional R410A Charge g/m 20 40
Maximum Height Difference Above / Below m 30 / 30 30 / 30

>
Max. Operating Current, cooling A 7.9 10.1
Suggested fuse Size A 10 16
Power Supply V-ph-Hz 220/240-1-50 220/240-1-50
Supply To Outdoor Unit Outdoor Unit
Interconnecting cables 3+E 3+E

Retail Price
Indoor Unit (panel included) £ 388.00 419.00
Outdoor Unit £ 835.00 1,215.00
System Price £ 1,223.00 1,634.00