Light Commercial - Digital Inverter Twin-split SystemsResidential
  • Allows connection of two indoor units (same type capacity) to one outdoor unit
  • Indoor units are in the same room, operate simultaneously and have a single controller
  • Twin-operation is possible with all light-commercial indoor units (except XT)
  • Precise capacity control at all conditions
  • Ideal for larger shops and open-plan offices
  • User-friendly controls
  • Performance tuning for optimised comfort
  • Requires a twin connection kit (RBC-TWP30E or 50E)*
  • Remote control is required (RBC-AMT32E)*
  • Ideal for R22 replacement
Outdoor Unit RAV SM1103AT-E SM1403AT-E SM1603AT-E SM1103AT-E SM1103AT-E SM1403AT-E SM1603AT-E
Indoor Unit   2 x 4-way ceiling cassette 2 x compact 2 x ceiling unit
      4-way cassette
  RAV SM564UT-E SM804UT-E SM804UT-E SM562MUT-E SM562CT-E SM802CT-E RSM802CT-E

Cooling Capacity Range kW 10.0 (3-11.2) 12.5 (3-13.2) 14.0 (3.0-16.0) 10.00 (3-11.2) 10.00 (3-11.2) 12.5 (3-13.2) 14.0 (3.0-16.0)
Heating Capacity Range kW 11.2 (3.0-13.0) 14 (3.0-16.0) 16 (3.0-18.0) 11.2 (3.0-12.5) 11.2 (3.0-12.5) 14 (3.0-16.0) 16 (3.0-18.0)
Power Input , cooling / heating kW 3.52 / 3.14 4.09 / 4.0 4.49 / 4.43 3.51 / 3.20 3.51 / 3.20 4.52 / 4.14 4.99 / 4.69
EER, Cooling / COP, heating W/W 2.84 / 3.57 3.06 / 3.50 3.12 / 3.61 2.85 / 3.50 2.85 / 3.50 2.72 / 3.38 2.81 / 3.41
Annual Power consumption, cooling kWh 1760 2045 2245 1755 1755 2260 2495
Energy Label, cooling / heating   C/B B/B B/A C/B C/B D/C C/B

UK Conditions - Cooling Capacity kW 10.87 12.81 15.33 10.87 10.87 12.81 15.53
UK Conditions - Sensible Cooling Capacity kW 6.67 5.25 6.67 8.15 11.10 8.15 11.10
UK Conditions - Heating Capacity kW 9.68 11.92 13.64 9.68 9.68 11.92 13.64
Retail Price                

Retail price, indoor units (2 off) £ 1,520.00 1,872.00 1,872.00 1,484.00 1,310.00 1,484.00 1,484.00
Retail price, outdoor unit £ 1,498.00 1,630.00 2,110.00 1,484.00 1,498.00 1,630.00 2,110.00
Retail price, twin kit (1103 - TWP30 / 1403 - TWP50) £ 50.00 53.00 not required 50.00 50.00 53.00 not required
Retail price, controller (RBC-AMT32E) £ 52.00 52.00 52.00 52.00 52.00 52.00 52.00
System Price £ 3,120.00 3,607.00 4,034.00 3,374.00 2,910.00 3,219.00 3,464.00


Outdoor Unit RAV SM1103AT-E SM1403AT-E SM1603AT-E SM1103AT-E SM1103AT-E SM1403AT-E SM1603AT-E
Indoor Unit   2 x ducted unit 2 x slim duct 2 x high-wall unit
  RAV SM564BT-E SM804BT-E SM804BT-E SM562SDT-E SM562KRT-E SM802KRT-E RSM802KRT-E

Cooling Capacity Range kW 10.0 (3.0-11.2) 12.5 (3.0-13.2) 14.0 (3.0-16.0) 10.00 (3.0-11.2) 10.00 (3.0-11.2) 12.0 (3.0-13.0) 14.0 (3.0-16.0)
Heating Capacity Range kW 11.2 (3.0-13.0) 14 (3.0-16.0) 16 (3.0-18.0) 11.2 (3.0-12.5) 11.2 (3.0-12.5) 14 (3.0-16.0) 16 (3.0-18.0)
Power Input , cooling / heating kW 3.56 / 3.14 4.42 / 4.03 5.12 / 4.69 3.548 / 3.14 3.48 / 3.214 4.52 / 4.24 5.10 / 4.98
EER, Cooling / COP, heating W/W 2.81 / 3.57 2.83 / 3.47 2.73 / 3.41 2.87 / 3.41 2.857 / 3.57 2.65/ 3.30 2.75 / 3.21
Annual Power consumption, cooling kWh 1780 2210 2560 1740 1740 2260 2550
Energy Label, cooling / heating   C/B C/B D/B B/B C/B D/C D/B

UK Conditions - Cooling Capacity kW 10.87 12.81 15.33 10.87 10.87 12.81 15.53
UK Conditions - Sensible Cooling Capacity kW 6.67 8.35 11.10 6.67 6.67 8.35 11.10
Retail Price                

Retail price, indoor units (2 off) £ 1,170.00 1,740.00 1,740.00 1,090.00 776.00 838.00 838.00
Retail price, outdoor unit £ 1,540.00 1,685.00 2,110.00 1,540.00 1,540.00 1,685.00 2,110.00
Retail price, controller (RBC-AMT32E) £ 52.00 52.00 52.00 52.00 52.00 52.00 52.00
System Price £ 2,762.00 3,477.00 3,902.00 2,682.00 2,368.00 2,575.00 3,000.00

Outdoor Unit RAV   SM1103AT-E SM1403AT-E SM1603AT-E

Airflow l/s 1250 1250 1717
Airflow m3/h 4500 4500 6180
Sound Pressure Level, cooling / heating dB (A) 53 / 54 53 / 54 51 / 53
Sound Power Level, cooling / heating dB (A) 70 / 71 70 / 71 68 / 70

Dimensions, Height x Width x Depth mm 795 x 900 x 320 795 x 900 x 320 1340 x 900 x 320
Weight kg 77 77 99

Operating Range - Cooling °C -15 to 43 -15 to 43 -15 to 43
Operating Range - Heating °C -15 to 15 -15 to 15 -15 to 15

Pipe Connections, Gas - Liquid in 5/8 - 3/8 5/8 - 3/8 5/8 - 3/8
Pipe Length, Maximum m 30 30 30
Pipe length, pre-charged m 30 30 30
Additional R410A Charge g/m 40 40 40
Maximum Height Difference Above / Below m 30 / 30 30 / 30 30 / 30

Max. Operating Current, cooling A 15.0 17.6 23.9
Suggested fuse Size A 20 20 25
Power Supply V-ph-Hz 220/240-1-50 220/240-1-50 220/240-1-50
Interconnecting cables   3+E 3+E 3+E