Light Commercial - Super Digital Inverter Heat Pump Systems, High-Wall Units Residential
  • New compact flat-panel design
  • Increased energy efficiency/cost savings
  • New fan motor and enhanced compressor design
  • Extended pipe runs / greater installation flexibility
  • More control steps for precise inverter control
  • Operating range down to -15°C (cooling)
  • EER values up to 3.88 in cooling mode
  • High performance heating, even at -15°C
  • Increased heat exchanger efficiency
  • Superior five-stage air filtration system
  • Ideal for R22 replacement




Outdoor Unit - RAV   SP564AT-E SP804AT-E
Indoor Unit (high-wall unit) - RAV   SM562KRT-E SM802KRT-E
Remote Control   Infra-red Infra-red

Cooling Capacity Range kW 5.0 (2.2 - 5.6) 6.9 (2.2 - 8.0)
Heating Capacity Range kW 5.6 (2.2 - 7.0) 8.0 (2.2 - 10.0)
Power Input , cooling / heating kW 1.39 / 1.55 2.40 / 2.40
EER, Cooling / COP, heating W/W 3.60 / 3.61 2.88 / 3.33
Annual Power consumption, cooling kWh 695 1200
Energy Label, cooling / heating   B/B C/C

UK Conditions - Cooling Capacity kW 5.44 7.76
UK Conditions - Sensible Cooling Capacity kW 4.22 5.85
UK Conditions - Heating Capacity kW 4.69 6.70

Indoor Unit (high-wall unit) RAV   SM562KRT-E SM802KRT-E

Air Flow (High/Medium/Low) l/s 178/208/233 203/243/308
Air Flow (High/Medium/Low) m3h 641/749/839 731/875/1109

Sound Pressure Level (Low/Medium/High) dB(A) 36/41/45 36/41/45
Sound Power Level (Low/Medium/High dB(A) 51/56/60 51/56/60

Dimensions, Height x Width x Depth mm 298 x 998 x 221 298 x 998 x 221
Weight kg 12 12

Outdoor Unit RAV   SP562AT-E SP802AT-E

Airflow l/s (m3/h) 944 (3400) 944 (3400)
Sound Pressure Level, cooling / heating dB (A) 46/ 47 47/ 49
Sound Power Level, cooling / heating dB (A) 63/ 64 64 / 66

Dimensions, Height x Width x Depth mm 795 x 900 x 320 795 x 900 x 320
Weight kg 55 62

Operating Range - Cooling °C -15 to 43 -15 to 43
Operating Range - Heating °C -15 to 15 -15 to 15

Pipe Connections, Gas - Liquid in 1/2 - 1/4 5/8 - 3/8
Pipe Length, Maximum / Minimum m 50/5 50/5
Pipe length, pre-charged m 20 30
Additional R410A Charge g/m 20 40
Maximum Height Difference m 30 30

Max. Operating Current, cooling A 7.17 8.95
Suggested fuse Size A 10 10
Power Supply V-ph-Hz 220/240-1-50 220/240-1-50
Supply To   Outdoor Unit Outdoor Unit
Interconnecting cables   3+E 3+E

Retail Price
Indoor Unit (panel included) £ 388.00 419.00
Outdoor Unit £ 1,015.00 1,510.00
System Price £ 1,403.00 1,929.00