RAS
Multi-Split Inverter Ducted Units, Heat Pumps
- High static pressure
- Slim design, only 230mm high
- Low noise, multi-split system
- Flexible air inlet below or at rear
- Drain pumpkit (optional extra)
- Several A-rated models
- Auto-diagnosis function
- Latest digital hybrid inverter technology
- Designed for use with refrigerant R410A
| Indoor Unit, ducted Unit | RAS-M10GDV-E | RAS-M13GDV-E | RAS-M16GDV-E | |||||||||
| Outdoor Unit Size | 14 | 18 | 26 | 27 | 14 | 18 | 26 | 27 | 18 | 26 | 27 | |
| Remote Controller Included | Infra Red | Infra Red | Infra Red | |||||||||
| Nominal Cooling Capacity | kW | 2.5 | 2.7 | 2.7 | 2.7 | 3.5 | 3.7 | 3.7 | 3.7 | 4.5 | 4.5 | 4.5 |
| Nominal Heating Capacity | kW | 3.2 | 4.0 | 4.0 | 4.0 | 4.2 | 5.0 | 5.0 | 5.0 | 5.2 | 5.5 | 5.5 |
| Power Input - Cooling | kW | 0.57 | 0.60 | 0.75 | 0.75 | 1.10 | 1.10 | 1.20 | 1.20 | 1.50 | 1.65 | 1.65 |
| Power Input - Heating | kW | 0.85 | 1.20 | 1.50 | 1.45 | 1.25 | 1.80 | 2.05 | 2.05 | 1.90 | 2.40 | 2.40 |
| EER - Cooling | W/W | 4.39 | 4.50 | 3.60 | 3.60 | 3.18 | 3.36 | 3.08 | 3.08 | 3.00 | 2.73 | 2.73 |
| Annual Power Consumption | kWh | 285 | 300 | 375 | 375 | 550 | 550 | 600 | 600 | 750 | 825 | 825 |
| Energy Label - Cooling | A | A | A | A | D | C | D | D | D | E | E | |
| UK Conditions | ||||||||||||
| Cooling Capacity | kW | 2.60 | 3.50 | 4.32 |
| Sensible Cooling Capacity | kW | 2.16 | 2.96 | 3.60 |
| Heating Capacity | kW | 3.70 | 4.60 | 5.05 |
| Indoor Unit, ducted type** | RAS-M10GDV-E | RAS-M13GDV-E | RAS-M16GDV-E | |
| Air Flow - Cooling (high/low) | l/s (m3/h) | 200/111 (720/400) | 217/119 (781/428) | 217/111 (781/428) |
| Air Flow - Heating (high/low) | l/s (m3/h) | 200/125 (720/450) | 217/133 (781/479) | 217/139 (781/500) |
| Sound Pressure - High / Low - Cool (High / Low - Heat) | dB(A) | 31/23 (31/24) | 32/24 (32/25) | 32/25 (33/28) |
| Sound Power - High / Low - Cool (High / Low - Heat) | dB(A) | 44/36 (44/37) | 45/37 (45/38) | 46/38 (46/41) |
| Ext. static pressure (std/max)* | Pa | 35.3 / 54.9 | 41.2 / 63.7 | 41.2 / 63.7 |
| Dimensions H x W x D | mm | 230 x 750 x 440 | 230 x 750 x 440 | 230 x 750 x 440 |
| Weight | kg | 19 | 19 | 19 |
| Retail Price (Per Indoor Unit) | £ | 434.00 | 494.00 | 591.00 |
| Outdoor Unit | RAS-M14GAV-E | RAS-M18GAV-E | RAS-3M26GAV-E | RAS-4M27GAV-E |
| Number of Indoor Units | 2 Room Multisplit | 2 Room Multisplit | 3 Room Multisplit | 4 Room Multisplit |
| EER / COP (Cooling / Heating) | W/W | 3.70/4.35 | 3.25/3.62 | 3.33/3.53 | 3.20/4.00 |
| Air Flow | l/s (m3/h) | 505 (1280) | 583 (2100) | 833 (3000) | 833 (3000) |
| Sound Pressure (Cooling / Heating) | dB(A) | 48/46 | 50/48 | 48/48 | 48/48 |
| Sound Power (Cooling / Heating) | dB(A) | 61/59 | 63/61 | 61/61 | 61/61 |
| Dimensions - H x W x D | mm | 550x780x290 | 550x780x290 | 795x900x230 | 795x900x230 |
| Weight | kg | 36 | 40 | 64 | 65 |
| Operating Range - Cooling / Heating | °C | 5 to 43 / -15 to 24 | 5 to 43 / -15 to 24 | 5 to 43 / -15 to 24 | 5 to 43 / -15 to 24 |
| Pipe Connections - Gas / Liquid | in | 3/8 - 1/4 | 3/8 - 1/4 | 3/8 - 1/4 | 3/8 - 1/4 |
| Pipe Length - Max - Unit / Total | m | 20/30 | 20/30 | 25/50 | 25/70 |
| Pipe Length - Pre-charged | m | 20 | 20 | 50 | 70 |
| Maximun Height Difference | m | 10 | 10 | 15 | 15 |
| Maximum Operating Current - Cooling | A | 6.9 | 7.2 | 10.8 | 10.6 |
| Suggested Fuse Size | A | 10 | 10 | 16 | 16 |
| Power Supply | V-ph-Hz | 220/240-1-50 | 220/240-1-50 | 220/240-1-50 | 220/240-1-50 |
| Supply To | Outdoor Unit | Outdoor Unit | Outdoor Unit | Outdoor Unit | |
| Interconnecting cables | 3+E | 3+E | 3+E | 3+E |
| Retail Price (Outdoor Unit) | £ | 912.00 | 1,012.00 | 1,660.00 | 2,055.00 |