TOSHIBA FAULT CODES
Fault Finding When You Need It!
At Cool Solutions we believe that one of the companies strengths the the Technical Support that we offer. We have created this web page to give engineers a simple tool for helping with fault finding.
Also, Click on the image to the right to download the latest Technical Handbook.
Select A Fault Code Or Click On The Search Button
On split A/C equipment it signifies an indoor to outdoor communication failure.
On VRF equipment it could also be attributed to communication breakdown between condenser PCB's.
Likely causes:
- Indoor PCB.
- Condenser PCB.
- Interconnecting Wiring.
- Fault with the transformer used to power condenser PCB.
This points towards a reverse change in temperature, detected by indoor evaporator sensor (TC).
Likely causes:
4 way valve.
4 way reversing valve energised for heating operation.
Faulty TC sensor.
Frost conditions detected / No temperature change.
Detected indoors by evaporator sensor (TC).
Likely causes:
Poor airflow.
Refrigerant Shortage. Overheating compressor.
Indoor fan trouble. Detected indoors.
Likely causes:
Fan motor.
Indoor PCB.
On a cassette, packing foam has not been removed.
EEPROM Failure on PCB.
Detected indoors (replace indoor PCB)
Inverter compressor PCB short circuit.
Detected at outdoor.
Likely causes:
Blown fuses supplying inverter pack.
Faulty IPDU (inverter board) or component within inverter pack.
Electrical fault on inverter compressor.
Multi-Controller box error.
Detected indoors (Interrogate Multi-Controller box for additional faults by setting display switch @ position 1)
Abnormal current detection on inverter compressor.
Detected at outdoor.
Possible causes:
IPDU PCB (Inverter board) faulty.
Compressor faulty.
Condenser coil sensor (TE) fault.
Detected indoors.
Likely causes:
TE/TE1 sensor condition / fault - sensor value 20°C=12.5k Ohms.
Outdoor PCB fault.
Liquid or Compressor discharge sensor fault.
Likely causes
TL,TD sensor condition / faulty - TL sensor value 20°C=12.5k Ohms, TD sensor value 20°C=63k Ohms
PCB faulty.
Condenser PCB faulty (Replace main PCB)
2 Pipe VRF & Split A/C equipment High Pressure switch activation 425psi-29bar.
3 Pipe VRF equipment, interrogate condenser PCB for additional fault code.
Detected at outdoor.
Likely causes:
Split A/C equipment faulty H.P. switch, restriction in refrigerant flow, fan motor failure, poor airflows.
VRF equipment, set condenser interface PCB switches as follows SW1 @ position 2 & SW2 @ position 0 (see sub codes Er21 or ErAd)
Excessive high pressure.
Detected at outdoor.
Likely causes:
Abnormal characteristics of Pd transducer.
Refrigerant restriction/blockage
Multi-Controller box Th(A) sensor fault.
Likely causes:
TH(A) sensor or M/C box PCB sensor value 20°C=12.5k Ohms
Multi-Controller box Th(B) sensor fault.
Likely causes:
TH(B) sensor or M/C box PCB sensor value 20°C=12.5k Ohms
Multi-Controller box Th(C) sensor fault.
Likely causes:
TH(C) sensor or M/C box PCB sensor value 20°C=12.5k Ohms
Multi-Controller box Th(D) sensor fault.
Likely causes:
TH(D) sensor or M/C box PCB sensor value 20°C=12.5k Ohms
Multi-Controller box Th(X) sensor fault.
Likely causes:
TH(X) sensor or M/C box PCB sensor value 20°C=12.5k Ohms
Phase missing / Phase Rotation.
Detected at outdoor.
Likely causes:
Abnormal power supply.
Multi-Control box does not recognise condenser capacity.
Likely causes:
Interconnecting cable damage.
Outdoor PCB fault.
Indoor capacity to high.
Likely causes:
Loss of combination within group of modularised condensers.
Indoor coil sensor fault.
Detected indoors.
Likely causes:
TC1 sensor condition - sensor value 20°C=12.5k Ohms.
Indoor PCB faulty.
Indoor coil sensor fault.
Detected indoors.
Likely causes:
TC2 sensor condition - sensor value 20°C=12.5k Ohms.
Indoor PCB faulty.
Communication failure on P&Q network (indoor/outdoor communication).
Detected indoors & outdoors.
Likely causes:
Network cable condition.
PCB failure, indoor or outdoor.
Indoor unit count too high.
Detected at outdoor.
Likely causes:
Indoor capacity vs. outdoor capacity Incorrect.
Too many indoor units connected.
Central control communication error.
Detected at central controller & indoors.
Likely causes:
Indoor power failure.
Central controller address error.
Cable damage.
Duplicated zone address.
Likely causes:
Incorrectly assigned central control addresses.
No communication from indoor to remote controller.
Detected by hard-wired remote controller.
Likely causes:
Faulty indoor PCB.
Remote controller faulty. Cable damage.
Indoor float switch open circuit as result of high condensation levels within drip tray.
Detected indoors.
Likely causes:
Faulty float switch.
Faulty lift pump. Drain blocked.
Return air sensor fault.
Detected indoors.
Likely causes:
TA sensor condition - sensor value 20°C=12.5k Ohms.
Indoor PCB faulty.
Coil sensor fault.
Detected indoors.
Likely causes:
TC sensor condition - Sensor value 20°c=12.5k Ohms
Indoor PCB fault
Outdoor error.
Detected indoors (Interrogate condenser units for additional faults)
High Inverter DC current.
Detected at outdoor.
Likely causes:
Imbalance in compressor voltage
Excessive amps drawn by inverter compressor
High compressor discharge temperature.
Detected at outdoor.
Likely causes:
Low refrigerant charge
Poor refrigerant flow, blockage
Poor airflows
TD sensor condition - sensor value 20°C=63k Ohms
High Inverter AC current.
Detected at outdoor.
Likely causes:
Imbalance in compressor voltage draw
Excessive amps drawn by inverter compressor
Outdoor unit quantity fallen (loss of communication between condensers).
Detected at outdoor.
Likely causes:
Power interruption
BUS communication Cable / wiring problem between condening units
Outdoor units quantity too high.
Detected at outdoor.
Likely cause:
Too many condensers connected
Outdoor unit address incorrect.
Detected at outdoor.
Likely causes:
Multiple modularised condenser having SW 9 ON
Interface PCB failure
No temperature change in evaporator.
Detected by indoor evaporator sensor TC1.
Likely causes:
Miss-wiring
Restriction in refrigerant flow
Refrigerant shortage
Insufficient temperature change on evaporator.
Detected indoors.
Likely causes:
Miss-wiring
Restriction in refrigerant flow
Refrigerant shortage
TC1,TC2 & TA sensor condition - sensor value 20°C=12.5k Ohms
Compressor discharge sensor fault.
Detected at outdoor.
Likely causes:
TD1/ThD1 sensor condition - sensor value 20°C=63k Ohms
Interface PCB faulty
Compressor discharge sensor fault.
Detected at outdoor.
Likely causes:
TD2/ThD2 sensor condition - sensor value 20°C=63k Ohms
Interface PCB faulty
Compressor suction sensor fault.
Detected at outdoor.
Likely causes:
TS1/ThS sensor condition - sensor value 20°C=12.5k Ohms
Interface PCB faulty
High compressor discharge temperature.
Detected at outdoor by TD1.
Likely causes:
Low refrigerant
Poor refrigerant flow
Airflows
TD2 sensor faulty - sensor value 20°C=63k Ohms
High compressor suction temperature > 40°C.
Detected at outdoor.
Likely causes:
Severe gas shortage
TS sensor condition - sensor value 20°C=12.5k Ohms
Interface PCB faulty
High side pressure sensor fault.
Detected at outdoor. (Replace Pd pressure transducer)
Pressure transducer error.
Detected at outdoor.
Likely causes:
Abnormal running pressures
Abnormal PS / Pd characteristics
Interface PCB faulty
High compressor discharge temperature @ low inverter speed.
Detected at outdoor.
Likely causes:
TD1 sensor condition - value 20°C=63k Ohms
Insufficient refrigerant sensor
Phase rotation incorrect.
Detected at outdoor.
Likely causes:
Abnormal phase order
Missing phase to outdoor unit
Low pressure transducer error or misreading fault.
Detected at outdoor.
Likely causes:
Incorrect characteristics of suction pressure transducer (PS) Interface PCB faulty

